Wholesale TJ0500 Gas Jet Burner Nozzles Industrial Burners for Steam Boilers New Condition for Manufacturing Plants
Generally speaking, the working conditions of ignition burners are relatively bad. They are easily subjected to high temperature radiation and flame scouring in the furnace for a long time, which can easily cause creep, high temperature deformation and damage. At the same time, some ignition burners have special working environment requirements: such as high positive pressure environment, high negative pressure environment, high airflow environment, high cold environment, special fuel environment, etc., which all need to be able to ignite reliably, burn stably, and have a certain flame rigidity. To ensure the ignition of the main combustion equipment
Description
Parameter |
Burner Velocity |
Model TJ0150 |
Model TJ0200 |
|
Max input, Btu/hr (KW) |
Medium / High velocity |
1,500,000(400) | 2,000,000(586) | |
Min input, Ratio regulated Btu/hr (KW) |
Medium / High velocity | 150,000(44) | 200,000(59) | |
Min input, Fixed air Btu/hr (KW) |
Medium / High velocity | 30,000(9) | 40,000(12) | |
Main Gas Inlet Pressure, "w.c. (mbar) Fuel pressure at gas inlet |
High velocity | Natural gas | 14.5(36.0) | 9.3(23.0) |
Propane |
15.0(38.0) | 12.7(32.0) | ||
Butane |
15.5(39.0) | 13.4(34.0) | ||
Medium velocity | Natural gas | 7.0(17.5) | 7.1(18.0) | |
Propane | 6.0(15.0) | 8.5(21.0) | ||
Butane | 6.5(16.0) | 6.9(17.0) | ||
Air Inlet Pressure, "w.c. (mbar) 15% excess air at maximum input |
High velocity | Natural gas | 17.5(44.0) | 12.3(31.0) |
Propane | 19.5(49.0) | 14.1(35.0) | ||
Butane | 19.5(49.0) | 14.1(35.0) | ||
Medium velocity | Natural gas | 9.5(24.0) | 10.0(25.0) | |
Propane | 10.0(25.0) | 11.0(28.0) | ||
Butane | 10.5(26.0) | 11.0(28.0) | ||
High Fire Visible Flame Length, inches (mm) Measured from the outlet end of the combustor |
High velocity | Natural gas | 38(965) | 27(685) |
Propane | 42(1065) | 30(760) | ||
Butane | 43(1090) | 30(760) | ||
Medium velocity | Natural gas | 43(1090) | 36(915) | |
Propane | 42(1065) | 32(810) | ||
Butane | 44(1120) | 32(810) | ||
Approximate Flame Velocity, ft/s (m/s) Approximately 15% excess air at maximum input |
High velocity | 500(152.4) | 500(152.4) | |
Medium velocity | 250(76.2) | 250(76.2) | ||
Flame Detection | UV scanners only (Can be used with all combustors) | |||
Fuel |
Natural gas, propane, butane For any other mixed gas, contact our company. |