+86 13928884373

Video Contact Us

All Categories

TJ Burner

Home >  Products >  Industrial Burner >  TJ Burner

Wholesale TJ0500 Gas Jet Burner Nozzles Industrial Burners for Steam Boilers New Condition for Manufacturing Plants

Generally speaking, the working conditions of ignition burners are relatively bad. They are easily subjected to high temperature radiation and flame scouring in the furnace for a long time, which can easily cause creep, high temperature deformation and damage. At the same time, some ignition burners have special working environment requirements: such as high positive pressure environment, high negative pressure environment, high airflow environment, high cold environment, special fuel environment, etc., which all need to be able to ignite reliably, burn stably, and have a certain flame rigidity. To ensure the ignition of the main combustion equipment

Description

.1

Blank_TJ0040 (1).jpgBlank_TJ0040 (2).jpgBlank_TJ0150 (1).jpgBlank_TJ0150 (2).jpgBlank_TJ0200 (1).jpg

Parameter
Burner Velocity
Model TJ0150
Model TJ0200
Max input, Btu/hr (KW)
Medium / High velocity
1,500,000(400) 2,000,000(586)
Min input, Ratio regulated Btu/hr (KW)
Medium / High velocity 150,000(44) 200,000(59)
Min input, Fixed air Btu/hr (KW)
Medium / High velocity 30,000(9) 40,000(12)

Main Gas Inlet Pressure, "w.c. (mbar)

Fuel pressure at gas inlet

High velocity Natural gas 14.5(36.0) 9.3(23.0)
Propane
15.0(38.0) 12.7(32.0)
Butane
15.5(39.0) 13.4(34.0)
Medium velocity Natural gas 7.0(17.5) 7.1(18.0)
Propane 6.0(15.0) 8.5(21.0)
Butane 6.5(16.0) 6.9(17.0)

Air Inlet Pressure, "w.c. (mbar)

15% excess air at maximum input

High velocity Natural gas 17.5(44.0) 12.3(31.0)
Propane 19.5(49.0) 14.1(35.0)
Butane 19.5(49.0) 14.1(35.0)
Medium velocity Natural gas 9.5(24.0) 10.0(25.0)
Propane 10.0(25.0) 11.0(28.0)
Butane 10.5(26.0) 11.0(28.0)
High Fire Visible Flame Length, inches (mm)
Measured from the outlet end of the combustor
High velocity Natural gas 38(965) 27(685)
Propane 42(1065) 30(760)
Butane 43(1090) 30(760)
Medium velocity Natural gas 43(1090) 36(915)
Propane 42(1065) 32(810)
Butane 44(1120) 32(810)
Approximate Flame Velocity, ft/s (m/s)
Approximately 15% excess air at maximum input
High velocity 500(152.4) 500(152.4)
Medium velocity 250(76.2) 250(76.2)
Flame Detection UV scanners only (Can be used with all combustors)
Fuel

Natural gas, propane, butane

For any other mixed gas, contact our company.

All information is based on laboratory testing in neutral (0 "w.c., 0 mbar) pressure chamber. Different chamber
conditions may affect the data.
All information is based on standard combustor design. Changes in combustor will alter performance and pressures.
All inputs are calculated according to the high calorific value of the fuel.
Our company reserves the right to change the construction and/or configuration of our products at any time without
being obliged to adjust earlier supplies accordingly.
Plumbing of air and gas will affect accuracy of orifice readings. All information is based on generally acceptable air
and gas piping practices.
TJ0200.jpg
TJ0200-1.jpg

_12_13_14_15

Get a Free Quote

Our representative will contact you soon.
Email
Mobile/Whatsapp
Name
Company Name
Message
0/1000